Info
These regulators are designed to reduce gas pressure from the first
stage regulator down to appliance pressure, normally 11” w.c. They
are for use in LP-Gas applications.
| Part Number | Inlet Connection | Outlet Connection | Orifice Size | Factory Delivery Pressure | Adjustment Range | Bonnet Vent Position | Vaport Capacity BTU/hr Propane* |
| LV6503B14 | 1½” F. NPT | 1½” F. NPT | ⅝” | 11” w.c. at 10 PSIG Inlet |
8½” - 14” w.c. | Over Inlet | 8,000,000 |
| LV6503B16 | 2” F. NPT | 2” F. NPT | 9,750,000 |
* Maximum flow is based on 10 PSIG inlet and 20% droop.