Info

These regulators are designed to reduce gas pressure from the first
stage regulator down to appliance pressure, normally 11” w.c. They
are for use in LP-Gas applications.

 

 

Part Number Inlet Connection Outlet Connection Orifice Size Factory Delivery Pressure Adjustment Range Bonnet Vent Position Vaport Capacity BTU/hr Propane*
LV6503B14 1½” F. NPT 1½” F. NPT ⅝” 11” w.c. at 10 PSIG
Inlet
8½” - 14” w.c. Over Inlet 8,000,000
LV6503B16 2” F. NPT 2” F. NPT 9,750,000

* Maximum flow is based on 10 PSIG inlet and 20% droop.